Fan Coil Unit Controls

TECHNICAL SPECIFICATIONS

Thermostat Enclosure:

High impact polycarbonate & ABS blend 2-piece vented housing. Screw mount back plate, snap on cover. 6.5" x 4.75" x 1.25"

Display:

LCD, multi-function reflective, 12 o'clock viewing angle

Ambient Ratings:

Temperature

- Operating Range: 0°C to 45°C

- Shipping and Storage Range: -20°C to 55°C

- Humidity Range 5 to 95% rh, non-condensing

Communication:

- 916.5 MHz Amplitude Shift Keyed

- Packet Protocol ANSI 709.1-1999

Control Methodology:

On/Off - control typically 1.5°F at 50% duty cycle

Setpoint Range: 50°F to 90°F (10°C to 30°C)

Temperature:

- Accuracy, ± 0.5°F

- Resolution, 1°F

Supply Voltages:

- Thermostat, 2 or 4 AA batteries

(Photovoltaic ambient light opportunity charging)

- Line-voltage RCN, 120, 208, 240vac

- Low-voltage RCN, 24vac control voltage

RCN Output:

Pilot duty solid-state relay outputs @ 0.5A max.

RCN Wiring:

Low-voltage RCN, 0.25" quick connect

Line-voltage RCN, color-coded flying leads

Energy Management Inputs:

(2) Dry form-A contacts with 5vdc pull-up

 