FAN COIL UNIT APPLICATION NOTE:
The
T9000 wireless RF thermostat with Plug-in Remote Control Node (RCN) can
quickly convert any 110vac FCU to precision, programmable temperature
control:
-
Turn off power to the FCU at the circuit breaker.
-
Disconnect the 110vac wiring feeding the fan speed selector box.
-
Install a standard 110vac receptacle using the FCU power wires.
-
Install a standard 110vac 14-gauge plug-cord with male end on the fan
speed selector box. (The cord is connected where the wires in step 2
above were removed.)
-
Plug a T9000 Plug RCN into the newly installed receptacle.
-
Plug the newly installed FCU male plug into the RCN and turn the FCU power back on.
-
Turn the fan speed switch to the speed you prefer.
-
Mount the T9000 thermostat in a suitable location and begin operating the FCU from the thermostat.

FLOW VALVE NOTE:
Whether a 2-pipe or 4-pipe system, flow control valves are typically
powered through the fan speed selector switch. Cycling power as
described will also work the flow valve in such configurations.
NOTES:
-
When installing, avoid locations that completely enclose the RCN behind sheet metal.
-
Do not exceed the Plug RCN load rating of 15 amps at 110vac.
-
Follow National and local electrical wiring codes, practices, guidelines and regulations.
|